247-IT Guide
UPS shutdown in the Windows event log: event IDs for your SIEM
An emergency shutdown that only exists in a log file on the host is invisible to the operations centre. The UPS Hyper-V Shutdown Monitor therefore writes its most important events with fixed event IDs to the Windows Application log, where Microsoft Sentinel, Splunk, Graylog, Wazuh or a PRTG sensor pick them up without additional agents. Which numbers exist, which ones deserve an alert, and what the queries look like.
Why the event log is the most reliable integration point
In a power outage, the first things to go are usually the ones alerts depend on: the switch to the internet router, the mail server, the Teams connection. An event in the local Windows log needs none of them. It is written the moment the service makes its decision and stays on disk until the host is back. The agent that forwards it catches up afterwards. Four reasons why the event log comes first in a SIEM integration:
- No new transport path — Sentinel via the Azure Monitor Agent, Splunk via the Universal Forwarder, Elastic via Winlogbeat, Wazuh via its agent, Graylog via Sidecar with Winlogbeat or NXLog: all of them already read the Windows event log. One more log in the collection rule is enough.
- Structured fields instead of text search — event ID, category and level (Information, Warning, Error) are managed by Windows itself. A detection rule filters on
EventID == 3000, not on a string in the message text. - Survives the loss of the alert channels — email, Teams or SMS can fail because the other end is unreachable. The event is there anyway and is delivered as soon as the collector sees the host again.
- Correlation with everything else — in the SIEM the emergency shutdown sits next to the hosts shutting down (system event 1074), the Hyper-V VMMS entries and the logons the next morning. The timeline of an incident comes from one source.
Source UpsHyperVShutdown in the Application log
The UPS Hyper-V Shutdown Monitor writes to the Windows Application log under the event source UpsHyperVShutdown. Both are fixed in the code and have to be entered exactly like that in collection rules, queries and filters. There is no separate log under “Applications and Services Logs”.
- Registration — the Windows service creates the source on every start if it is missing. That needs local administrator rights once, which it has as
LocalSystem. The installer does not register the source itself. - Without rights — if the source cannot be created or is missing, writing fails silently. The service keeps running normally, only the entries are missing. A desktop app without the service does not create the source; it writes events only if a service has registered the source before.
- Edition — the events belong to the monitoring integration of the Enterprise edition, together with the health endpoint. Pro licenses activated before September 4, 2026 keep the feature. It is active during the trial.
- Two exceptions — the licensing notices 1100 to 1104 are written by every edition, because they explain why something is missing due to the license. The integrity messages 1300 and 1301 belong to Tamper Protection and are written from Pro upwards.
- Category as a number — the task category is derived from the number block: 1 Service, 2 Licensing, 3 Monitor, 4 EmergencyShutdown, 5 HostShutdown, 6 Migration, 7 Audit, 8 Integrity. The application registers no category resource file, so Event Viewer shows the number.
The message text is English and follows fixed patterns: UPS events start with
UPS '<name>':, host events with Hyper-V host '<name>' (<hostname>),
audit events with Remote web interface audit: <type> — user '<user>' from <IP>.
These patterns are suitable for extracting UPS name, host or user. The rule itself should still
hang on the event ID, because only that is covered by the stability commitment in section 03.
All event IDs by block
The reference documentation phrases the commitment like this: “Once published, event IDs keep their meaning permanently. A new kind of event gets a new number in the matching block; existing numbers are never reused or repurposed.” The numbers have been in use since version 1.7.15 from August 31, 2026; later versions added blocks and changed none. For some IDs the level depends on state: the same number reports the onset as a warning and the end as information.
| ID | Level | Edition | Meaning |
|---|---|---|---|
| Service · 1000–1099 · category 1 | |||
| 1000 | Information | Enterprise | Service started, license check passed |
| 1001 | Information | Enterprise | Service stopped normally |
| 1002 | Information | Enterprise | config.json changed, monitoring restarts with the new configuration |
| 1003 | Information | Enterprise | Service restart requested via the remote web interface |
| 1004 | Error | Enterprise | Monitoring aborted with an unexpected exception, rebuilt after 30 s |
| 1005 | Error | Enterprise | Service crashed, stops with an error exit code; the recovery options restart it |
| 1006 | Warning | Enterprise | Service stop requested during a running emergency shutdown, the stop waits up to 15 min |
| Licensing · 1100–1199 · category 2 | |||
| 1100 | Error | all | Service blocked, no valid license, no monitoring |
| 1101 | Information | all | License valid again, monitoring resumes |
| 1102 | Error | all | Edition allows only one UPS; further UPS units, hosts or additional servers remain unprotected |
| 1103 | Warning | all | Remote web interface enabled but not licensed |
| 1104 | Warning | all | Monitoring-only mode configured, Enterprise license status changed at runtime; the mode from start-up applies until the monitor restarts |
| Web interface audit · 1200–1299 · category 7 | |||
| 1200 | Information | Enterprise | Login succeeded (user, IP, role) |
| 1201 | Warning | Enterprise | Login failed (entered name, IP; the password is not in the event) |
| 1202 | Warning | Enterprise | IP temporarily locked out after too many failed attempts, once per lockout |
| 1203 | Information | Enterprise | Logout |
| 1204 | Information | Enterprise | Initial setup completed, first account created |
| 1205 | Information | Enterprise | Account created, role or password changed, account deleted |
| 1206 | Information | Enterprise | Setting saved via the web interface (section and path) |
| 1207 | Information | Enterprise | Action triggered, such as service restart, self-test, license, configuration backup |
| 1208 | Warning | Enterprise | Access denied, such as a write attempt by a read-only account |
| Integrity · 1300–1399 · category 8 | |||
| 1300 | Warning | Pro and up | Tamper Protection: config.json changed outside the application, content does not match the signature; once per changed content |
| 1301 | Information | Pro and up | External change acknowledged and re-signed, with user; warning if acknowledging failed |
| UPS monitoring · 2000–2099 · category 3 | |||
| 2000 | Information | Enterprise | Monitoring of a UPS started (host, protocol) |
| 2001 | Information | Enterprise | Monitoring of a UPS stopped |
| 2002 | Information | Enterprise | Mains back after a triggered shutdown, monitor re-armed for the next outage |
| 2003 | Warning | Enterprise | Monitoring only: critical threshold reached, deliberately no shutdown |
| 2004 | Warning / Information | Enterprise | Warning threshold (battery charge, load, temperature, input voltage) exceeded or back in the normal range |
| 2005 | Information | Enterprise | UPS self-test started, manually or on schedule |
| 2006 | Warning | Enterprise | Self-test not started: precondition not met or rejected by the UPS |
| 2007 | Warning / Information | Enterprise | UPS on bypass, load not protected by the battery, or bypass left |
| 2008 | Warning / Information | Enterprise | Active UPS alarms changed (RFC 1628, Eaton XUPS, NUT ups.alarm), text names the alarms, or all alarms cleared |
| Emergency shutdown · 3000–3099 · category 4 | |||
| 3000 | Error | Enterprise | Emergency shutdown triggered or extended to previously deferred targets; the most important event for alerting |
| 3001 | Information | Enterprise | Running emergency shutdown cancelled, mains returned within the abort window |
| 3002 | Error | Enterprise | Shutdown attempt failed with an unexpected exception, the next poll tries again |
| Result per host · 3100–3199 · category 5 | |||
| 3100 | Information | Enterprise | Hyper-V host shut down with its VMs (duration in seconds); also for an additional server that reached its own runtime threshold |
| 3101 | Error | Enterprise | Shutdown of a Hyper-V host failed (error text) |
| 3102 | Error | Enterprise | Time budget of a host or shutdown-order group exceeded, the sequence continues in the background |
| Live migration · 4000–4099 · category 6 | |||
| 4000 | Information | Enterprise | Live migration of the VMs to a healthy partner node started, instead of a shutdown |
| 4001 | Error | Enterprise | Live migration failed |
The “Edition” column says who writes the event: “Enterprise” stands for the monitoring integration including the grandfathered Pro licenses mentioned above, “all” for every edition, “Pro and up” for Pro and Enterprise. Web interface events additionally require the interface to be enabled.
Which IDs deserve an alert
Not every event with level “Error” belongs on the on-call phone, and not every warning is harmless. A workable split for the first set of rules:
- Alert immediately —
3000emergency shutdown triggered,4000live migration instead of shutdown,1300configuration changed outside the application,1005service crashed. Something is happening right now that people need to know about. - Review within a working day —
1100and1102license blocked or too small,1104operating mode and license no longer match,3101and3102a host was not shut down cleanly,4001migration failed,2007UPS on bypass,2006self-test not started. - As a threshold rule —
1201more than five failed logins from one IP in ten minutes, every1202lockout, every1208access denied. Single failed attempts are everyday life, clusters are not. - A missing event as a signal —
1000and2000should follow every service start. If1000does not appear after a planned restart, the service was not started or the source is missing. If2002is still missing days after a3000, the monitor is not re-armed yet. - History only —
1001to1003,1200,1203to1207,2001,2005,3001,3100: these entries need no rule, but they make the timeline of an incident readable.
Event 3000 appears once per power outage, plus one entry when a previously deferred
UPS or host is shut down after all. Repeated shutdown attempts for the same outage do not
produce another 3000. What the shutdown means for domain controllers and why a DC
should go last is covered in the guide
Active Directory and power outages.
Queries for Sentinel, Splunk, Event Viewer and PowerShell
Microsoft Sentinel. The Azure Monitor Agent delivers the Application log through
a data collection rule into the Event table. The fields there are
Source, EventID, EventLevelName, EventCategory
and RenderedDescription. Include the Application log in the collection rule,
otherwise nothing arrives.
// Emergency shutdowns in the last 7 days
Event
| where Source == "UpsHyperVShutdown"
| where EventID == 3000
| where TimeGenerated > ago(7d)
| project TimeGenerated, Computer, EventID, RenderedDescription
// Every error from this source, grouped by ID and category
Event
| where Source == "UpsHyperVShutdown" and EventLevelName == "Error"
| summarize count() by EventID, EventCategory
Splunk. The Universal Forwarder with the Splunk Add-on for Windows files the
entries under source="WinEventLog:Application"; the source is called
SourceName there, the ID EventCode.
source="WinEventLog:Application" SourceName="UpsHyperVShutdown" EventCode=3000
| table _time, host, EventCode, Message
source="WinEventLog:Application" SourceName="UpsHyperVShutdown"
| stats count by EventCode, Type
Event Viewer. A custom view with an XML filter shows all shutdown events of a host without a SIEM. Under “Create Custom View” choose the “XML” tab and enable “Edit query manually”.
<QueryList>
<Query Id="0" Path="Application">
<Select Path="Application">
*[System[Provider[@Name='UpsHyperVShutdown']
and (EventID >= 3000 and EventID <= 3199)]]
</Select>
</Query>
</QueryList>
PowerShell. For checks on the host or via remoting; the filter hashtable uses the log's index and stays fast even on large logs.
Get-WinEvent -FilterHashtable @{
LogName = 'Application'
ProviderName = 'UpsHyperVShutdown'
Id = 3000, 3001, 3002, 3100, 3101, 3102
} -MaxEvents 50 |
Format-Table TimeCreated, Id, LevelDisplayName, Message -AutoSize -Wrap
Wazuh, Graylog, Elastic, PRTG. For the remaining systems, channel and provider
are all you need: channel Application, provider name UpsHyperVShutdown.
The Wazuh agent reads the channel in eventchannel format and exposes the ID as a
field of the system data; Winlogbeat and NXLog for Graylog or Elastic carry provider, channel
and event ID as separate fields. PRTG ships a sensor for the Windows event log that can filter
by log, source and event ID (vendor information as of October 2026, PRTG manual). The field
names depend on the collector; the numbers from section 03 are the same everywhere.
Event log, health endpoint, alert channels and support bundle
UPSmonitor offers three ways out that do not replace one another:
- Health endpoint —
/health,/metricsand/prtgdeliver the current state on request: level Ok, Warning, Critical or Unknown, battery charge, runtime, host reachability. For dashboards and availability monitoring. Setup in the guide UPS in PRTG, Zabbix and Prometheus. - Alert channels — email, Microsoft Teams, SMS, webhook, SNMP trap report actively to people, in the language of the alert configuration and with a status block. For on-call. See UPS alerts via Microsoft 365, Teams and SMS.
- Event log — history with fixed IDs for systems that collect Windows events anyway. For correlation, other teams' rules and evidence.
Support bundle. The export from the desktop app or the web interface contains
the file windows_eventlog.txt with this source's events from the last 30 days, each
entry with timestamp, level, EventID and category. Two uses: test a SIEM rule offline against real
entries before it goes live, and include the sequence of events with a support request without
granting access to the system. License keys and configured secrets are removed from the text
files before export.
Evidence. Anyone subject to NIS2 or comparable requirements has to detect, handle and document incidents. A time-stamped event with a stable ID, collected and retained centrally, is one building block for that, no more. Which retention, reporting deadlines and evidence apply in your case is a matter for your legal counsel or data protection officer. What else the software brings for signatures, encryption and audit is on the Security page.
SIEM integration checklist
- Source present — after a service restart, event 1000 appears in Event Viewer under Windows Logs, Application. If it is missing, the service was not started as a service or the license does not include the monitoring integration.
- Application log in the collection rule — data collection rule, inputs.conf, Winlogbeat or agent configuration include the
Applicationchannel; many templates collect only Security and System. - Test event checked — in test mode a triggered emergency shutdown writes event 3000 without sending real commands to hosts; 3100 only appears with a real shutdown. Trigger battery operation in a maintenance window and check that 3000 arrives in the SIEM with source and ID as separate fields.
- Rules created — at least 3000, 1300 and 1005 as alerts, 1201 as a threshold, 1100 and 1102 as tickets. Rules hang on the EventID, not on the message text.
- Web interface in view — if it is enabled, 1200 to 1208 come along; a read-only account for the operations centre produces 1208 on write attempts.
- Retention settled — the local Application log overwrites itself by size; retention in the SIEM follows your own requirements. The support bundle covers 30 days.
- After every update — check the release notes for new event IDs; existing numbers stay, new blocks may be added. For the service itself see UPS monitoring without shutdown.
Frequently asked questions
Which edition writes the events to the Windows event log?
The monitoring integration with the blocks service, UPS, emergency shutdown, hosts, migration and audit belongs to the Enterprise edition. Two blocks are written regardless: licensing notices 1100 to 1104 in every edition, integrity messages 1300 and 1301 from Pro upwards. During the 30-day trial all blocks are active. Pro licenses activated before September 4, 2026 keep the monitoring integration.
Why does Event Viewer show no entries from the source UpsHyperVShutdown?
The Windows service creates the source when it starts; that needs administrator rights once, which it has as LocalSystem. If only the desktop app runs without the service, the source is not created and writes fail silently. The second cause is the license: without an Enterprise license only the licensing and integrity blocks appear. Check first whether event 1000 shows up after a service restart.
Do the event IDs change with an update?
The reference documentation commits to this: once published, event IDs keep their meaning permanently, a new kind of event gets a new number in the matching block, and existing numbers are not reused or repurposed. The message text, however, may change. Bind detection rules to EventID and source, not to the text.
Does the event log replace the email or Teams alerts?
No. The event log is passive: someone has to collect and evaluate it, otherwise nobody notices the entry. The alert channels report actively, but need a working network to the outside for that. The two complement each other: the alerts reach the on-call engineer, the SIEM keeps the complete history and correlates it with other sources.
More guides
UPS in PRTG, Zabbix and Prometheus
The health endpoint for state and dashboards.
UPS alerts via Microsoft 365, Teams and SMS
Graph instead of SMTP AUTH, Workflows instead of connectors.
Active Directory and power outages
Why the domain controller goes last and comes back first.
Security
Signatures, encryption, audit and what leaves the network.
UPS monitoring without shutdown
Monitor and alert without shutting anything down.
Hyper-V on Server Core in a power outage
Service, web interface and events without a local GUI.
SNMPv3 on a UPS network card
authPriv with SHA and AES instead of a plain-text community.
Hyper-V failover cluster power outage
Coordinating quorum, CSV and live migration.
Shutting down Hyper-V VMs in a power outage
Stop action, shutdown order and time budget for an orderly shutdown.
Backup server and NAS in a power outage
Shutting down additional servers with their own runtime threshold.
Restarting after a power outage
Starting servers, storage and VMs automatically when power returns.
Trace every shutdown in your SIEM
30 days free, every feature included. With fixed event IDs in the Windows event log, a health endpoint for PRTG, Zabbix and Prometheus, and the audit log of the web interface.