What's new?

Current version v1.15.0 — new features, improvements and bug fixes per release, listed chronologically. Download now →

01 Version history Newest first. Items marked "Pro" apply to the Pro edition only, "Enterprise" to the Enterprise edition only.

Version history

v1.15.0 November 9, 2026
  • New ENTERPRISE: NOC display for wall screens — a full-screen page of the web interface with large UPS tiles (problems first), the reachability of all hosts and a banner while an emergency shutdown is running. It refreshes every 15 seconds. Access via a dedicated read-only link without login that can be revoked at any time.
  • New ENTERPRISE: Sites per UPS. The NOC display, dashboard and reports group or filter by site; alerts also go to dedicated recipients per site, optionally with a separate monthly report.
  • New ENTERPRISE: Maintenance mode per UPS — holds back alerts for 30 minutes to 72 hours, for example during a battery replacement. The shutdown logic stays active; start and end are reported on all alert channels.
  • New ENTERPRISE: Critical alerts can be acknowledged. Until then the alert is repeated and, after a configurable time, escalated to dedicated recipients by email or SMS.
  • New ENTERPRISE: Syslog channel per RFC 5424 over UDP, TCP or TLS, with a severity per event — for syslog servers and SIEM without Windows event forwarding.
  • New ENTERPRISE: Battery replacement reminder based on installation date and interval (default 48 months), 30 days ahead and once due.
  • New ENTERPRISE: Check shutdown readiness without shutting down: pending restart, the VMs’ “Shutdown” integration service, directly assigned devices and live migration authentication.
  • Improved PRO: “Test Migration” checks the live migration authentication method (CredSSP or Kerberos) and Credential Guard — important from Windows Server 2025 on, where CredSSP migration no longer works on domain members by default.
  • New: Templates for Grafana and Zabbix and a guide for Checkmk in the monitoring documentation. They follow the metrics reference; an import test in Grafana and Zabbix is still pending.
v1.14.1 November 8, 2026
  • New: Legrand UPS units with CS101/CS102 network card (Keor, Daker DK) are read directly via SNMP using the PPC MIB — status, battery charge, runtime, temperature, voltages, load and bypass. Values follow the vendor documentation; a check against a real device is still pending.
  • Improved ENTERPRISE: In “Monitoring only” mode, configured Hyper-V hosts and additional servers are ignored completely — no reachability checks, no alerts, no effect on the overall status.
  • Improved: The web interface shows the reason next to the overall status, e.g. “Warning (2 hosts unreachable)”.
  • Fixed: Invalid readings (“NaN”, “Infinity”) from NUT or SNMP counted as 0 % battery and could trigger a shutdown; very large runtimes overflowed.
  • Fixed: A UPS reporting “shutdown imminent” (NUT FSD, SNMP alarm) no longer counts as a healthy redundant UPS — the shutdown is no longer postponed on every poll.
  • Security: Names from the configuration no longer appear as clickable links in Teams, Slack, Discord and email. The web interface login lockout also applies per account; the update check only accepts HTTPS.
v1.14.0 November 3, 2026
  • New ENTERPRISE: Import a UPS list from CSV or Excel — create or update many UPS units at once, in the desktop app and in the web interface, with a template. A preview shows every row as new, existing or with errors; existing UPS units are only updated on request. Credentials are stored encrypted, formulas and macros from the file are never executed.
  • New: Flapping detection — if the supply switches repeatedly between mains and battery, from the third change within ten minutes a single “Unstable mains” message replaces the individual alerts, followed later by an all-clear. The shutdown logic is not affected.
  • Improved: The UPS name appears in the subject and in the first line of the power outage, power restored, battery critical, bypass, reachability and status report messages.
  • Fixed: The CSV export on the Reports tab of the desktop app protects the UPS name like the web interface — a name starting with “=” is no longer executed as a formula in Excel.
v1.13.0 October 30, 2026
  • New: Own license keys — besides the keys from the Polar shop there are license keys starting with “UPSM-”, for example when buying on invoice or through partners. The app validates them with the license server license.upsmonitor.de; Polar keys work as before.
  • New: A UPSM license is only blocked after an unambiguous, signed rejection by the license server; a proxy or error page starts the 7-day grace period. A change of machine (hardware replacement, VM moved to another Hyper-V host) is accepted.
  • New: Purchase on invoice for businesses based in Germany (page in German) — order without Polar, pay by bank transfer, license keys after payment has been received.
  • New: Socomec NetVision 5 and 7 — the card’s alarm table is evaluated (e.g. battery low, bypass, emergency stop, rectifier or module fault); “battery low” and an announced shutdown affect the shutdown logic.
v1.12.7 October 29, 2026
  • New PRO: Three-phase UPS units — the desktop app and web interface show the readings per phase L1–L3 (voltage, current, power and load, as far as reported), via SNMP (RFC 1628, Eaton, Socomec, Huawei) and NUT.
  • New ENTERPRISE: Phase readings also in the health endpoint, as Prometheus metrics and PRTG channels; the warning thresholds evaluate the least favourable phase.
  • Improved PRO: More readings are more precise and complete — APC with tenths and output power, CyberPower with output power, Socomec NetVision with its own readings and the EMD environmental sensor.
  • Fixed: Eaton did not show the environmental sensor humidity, Socomec NetVision 5 reported no battery temperature.
  • Fixed ENTERPRISE: “Monitoring only” silently switched to automatic shutdown when the license expired during operation. The license state now applies until the next start, and a change is reported.
  • Changed: The confirmation dialog of the manual emergency shutdown now says that it overrides “monitoring only”.
v1.12.6 October 26, 2026
  • New PRO: More readings on the dashboard of the desktop app and web interface: temperature, battery voltage, input and output frequency, output voltage, output current and output power, plus temperature and humidity from a connected environmental sensor — if the UPS reports these values via SNMP or NUT.
  • New ENTERPRISE: The readings are also available as Prometheus metrics (/metrics, now including input voltage) and as PRTG channels (/prtg).
  • Security: The bundled .NET runtime is updated to 10.0.14 (Microsoft security update of October 25, 2026), and the cryptography libraries to patched versions.
v1.12.5 October 10, 2026
  • Fixed: On Full HD screens, the dialog for adding and editing a Hyper-V host extended beyond the screen edge. It now uses two columns and is never taller than the screen; Save and Cancel always stay visible.
  • Fixed: Without a UPS set up (e.g. right after installation), the dashboard showed “BYPASS” and empty warning boxes. It now shows a hint to add a UPS on the “UPS Settings” tab.
  • Fixed: New UPS units get sequential names in the web interface and the desktop app (“UPS 2”, “UPS 3” …) instead of always “UPS 1”.
  • Improved: Update notices stay compact — the banner shows the first item with “(+N more)”, and the release notes scroll in the updater.
  • Changed: For the “Service only” installation type (Server Core), the remote web interface ENTERPRISE is now preselected and can still be deselected. The English setup shows the installation types in English.
v1.12.4 October 2, 2026
  • Fixed: With slow SNMP network cards (e.g. Eaton Network-M2 using SNMP v1), the bypass indicator and UPS alarms occasionally disappeared for one polling cycle. If the alarm table cannot be read completely, the last complete state is now kept for up to three cycles.
  • Improved: For Eaton network cards, queries these cards do not answer are skipped — about 30 fewer requests per poll with SNMP v1.
  • New: The Eaton alarm “Load unprotected” (Network-M2) is shown as such and triggers the PRO notification.
  • Fixed: Bypass is now also detected on Eaton/MGE cards (Galaxy, Pulsar, older Network-MS) and Socomec NetVision 5 — and for Socomec, Vertiv, Huawei, CyberPower and MGE even if the card also answers RFC 1628.
  • Fixed: If the UPS reports an imminent shutdown in its alarm table, it is treated like the NUT FSD signal and triggers the orderly shutdown. “Low battery” from the alarm table counts as LOW BATTERY while on battery.
  • Fixed: Battery faults are now detected while on mains as well, including “battery bad” and the new alarm “battery not connected” — previously they only showed up during a power outage.
  • Fixed: A NUT runtime calibration (“OB CAL”) no longer triggers a shutdown and is shown as a notice.
v1.12.2 October 1, 2026
  • Fixed: When the UPS runs on bypass, the desktop app and the web interface now show it clearly — a yellow “BYPASS” badge next to the status with a note that the load is not protected by the battery. Previously only “Online” was shown. Eaton maintenance bypass is detected as well.
  • New: Active UPS alarms such as general fault, internal failure, inverter, fan or charger failure are read from the UPS alarm table and shown on the dashboard — via SNMP (RFC 1628 and Eaton) and NUT, in all editions. Also written to the Windows Event Log (event IDs 2007/2008).
  • New PRO: “UPS reports an alarm” notification via all configured alert channels, with an all-clear once no alarms remain.
  • New ENTERPRISE: Health endpoint, Prometheus and PRTG report bypass and active alarms; both raise the overall status to “Warning”.
  • Security: Hardening from a security audit, including clickjacking protection for the web interface, validated NUT UPS name, hardened data folder and safe configuration restore. The health endpoint token can be restricted to the Authorization header.
v1.12.1 September 24, 2026
  • Fixed PRO: Tamper protection now visibly reports a change to the configuration file made outside the application — until now the finding was only written to the service log. New: a warning banner on the dashboard of the desktop app and the web interface with "Confirm change", a notification over every configured alert channel, an audit log entry and Windows event 1300 (confirmation: 1301).
  • Fixed: Each change is reported exactly once, even when the service and the desktop app detect it at the same time. A process without access to the signing key no longer raises a false alarm.
v1.12.0 September 24, 2026
  • New ENTERPRISE: Additional users for the remote web interface — any number of accounts besides the primary one, as administrator or "read-only". Read-only accounts see everything but cannot change or trigger anything. Managed in the web interface and in the desktop app; every account can change its own password under "My account".
  • New ENTERPRISE: Audit log — logins, failed attempts, lockouts, user management and every change with its result, filterable and exportable as CSV, additionally in the Windows Event Log (event IDs 1200–1208).
  • Changed ENTERPRISE: In the "monitoring only" operating mode, the desktop app and the web interface hide every setting that only serves the shutdown. The saved values are kept.
  • Fixed: The overall status on the web interface dashboard was English even in the German interface.
v1.11.1 September 23, 2026
  • Fixed ENTERPRISE: For "service only" installations with the remote web interface, the installer's final message now mentions the one-time setup token for the initial setup — where it is stored and how to read it.
v1.11.0 September 23, 2026
  • New ENTERPRISE: UPS monitoring — "monitoring only" mode (globally or per UPS: alert without shutting down), warning thresholds per UPS for battery charge, load, battery temperature and input voltage, and the UPS self-test via SNMP or NUT, manually or on a schedule.
  • New: Vertiv (Liebert), Huawei and CyberPower are read directly via SNMP — even when RFC 1628 is not enabled on the network card.
  • New: SNMP traps in the standard UPS-MIB format (RFC 1628) for new installations; existing installations keep the previous format.
  • Changed PRO: Microsoft Teams now works only via a Workflows webhook. Please switch existing Teams alerts to the workflow URL in the alert manager — the previous Graph API route could not send messages.
  • Fixed PRO: With multiple UPS devices, an outage now shuts down only the hosts of the affected UPS instead of the entire environment.
  • Fixed: Numerous improvements from a code review — shutdown sequence, Hyper-V connections, SNMP polling and service stability; a damaged configuration file is no longer overwritten with defaults.
  • Fixed ENTERPRISE: The remote web interface on a "service only" install without an Enterprise license now shows license management, so an Enterprise key can be entered without the desktop app. Initial setup is protected by a one-time setup token.
  • Security: The updater additionally verifies the setup's digital signature.
v1.10.0 September 23, 2026
  • Fixed: SNMP parsing for Socomec, APC and Eaton UPS devices corrected against the official vendor MIBs and Network UPS Tools drivers. Socomec previously triggered a false shutdown when the UPS was on mains but the battery was weak or faulty; APC runtime was never read due to a parser bug, so the runtime threshold never fired; on Eaton devices a misread OID caused a persistent false "replace battery" warning. Model, serial number and manufacturer are now read correctly for all three vendors.
  • New: The entire user interface is now fully bilingual (German/English) — every previously hardcoded text in dialogs, log messages and the updater now follows the selected language. Application logs are now uniformly in English.
  • New: For large UPS fleets: a switchable compact view (table instead of tiles) on the dashboard, a new PDF export covering all UPS devices at once (GUI and web interface), and a revamped web dashboard with a fleet overview and a "problems only" filter.
  • New: UPS model and serial number are now saved during setup instead of being queried fresh before every report — reports are faster and stay complete even if a UPS is briefly unreachable.
v1.9.5 September 13, 2026
  • Fixed: The "What's New" dialog could push its own Close button off the bottom of the window when the release notes were long enough to hit the window's height cap — the button was left barely visible as a thin sliver. The content area now scrolls on its own, and the Close button stays fixed and always visible.
  • New: Added a step-by-step in-app FAQ guide for the generic webhook alert channel — how to get a webhook URL from Slack, Discord, n8n, Zapier or your own endpoint, enter it, and test it.
v1.9.4 September 12, 2026
  • Fixed: The in-app FAQ's walkthrough for Microsoft 365 sign-in via device code (no client secret) ended right after the Azure setup, without saying where to enter the values in the app or that you then need to click "Request Device Code". Added.
  • Fixed: Two channel names in the in-app FAQ didn't match the actual on-screen section titles — corrected.
v1.9.3 September 11, 2026
  • New PRO: Servers can now get their own, earlier runtime threshold for shutdown — once the UPS runtime drops to this value, only that server is shut down immediately, independent of the global threshold. Useful for less critical systems that should be sacrificed early to save battery runtime for more important ones.
  • New ENTERPRISE: The remote web interface can now be set up directly from the desktop app — a new "Remote Web Interface" tab in General Settings covers port, bind address, IP allow-list and credentials. The installer now offers the web interface on a "service only" install as an explicit, unchecked option instead of enabling it automatically.
  • New PRO: The service can now notify you automatically when a new version is available (opt-in under Alerts → Triggers), and the web interface's own network settings can now be edited directly in the web interface itself, without a local GUI.
  • Fixed: Username for Hyper-V hosts and servers is now a required field. Without a username, the WinRM connection silently fell back to the Windows identity of the running process — for the Windows service, by default an account without the necessary Hyper-V rights. A connection test from the GUI could appear successful while the real emergency shutdown via the service would have failed unnoticed.
  • Fixed PRO: Several corrections to the new per-server early shutdown feature — it now requires several consecutive confirmations like every other trigger instead of acting on a single reading, a too-tight time budget could no longer block the entire emergency shutdown, and a server shut down early is now correctly made available again for the next outage.
  • Fixed: An expired session could make the web interface's service page unusable. A Hyper-V host newly created via the web interface was missing a pre-selected UPS, which excluded it from the Host SLA report and from a real emergency shutdown.
  • Fixed: On a maximized main window, Save/Add buttons could disappear behind the taskbar; the window's minimum size is now enforced reliably.
v1.9.2 September 7, 2026
  • Fixed: A power-outage forced-shutdown signal from the UPS (FSD) could, in rare timing windows, be overridden by a brief status flicker back to "online" — either cancelling an emergency shutdown that was still required, or preventing the software from re-arming after mains power returned.
  • Fixed: When multiple shutdown-order groups were configured, a single unresponsive host in an early group could delay later groups far beyond the configured runtime threshold. Shutdown groups now share one overall time budget.
  • Fixed ENTERPRISE: The Monitoring lock screen in the desktop app incorrectly said the feature was included in the Pro edition; it has required the Enterprise edition since v1.9.0. Existing Pro licenses keep their access as before, only the wording was wrong.
  • Fixed ENTERPRISE: An unexpected error in the remote web interface could go completely unlogged, including in the Support Bundle. Such errors are now always recorded in the service log.
v1.9.1 September 4, 2026
  • New ENTERPRISE: Remote web interface for Windows Server Core without a local GUI — a dashboard with a battery/load history chart, UPS/host/extra-server configuration, reports, topology, log/history, service control, and emergency shutdown, all through the browser over HTTPS with login and session protection.
  • New ENTERPRISE: Custom UPS OID profiles and your own TLS certificate can be uploaded directly through the web interface, alongside configuration backup and restore.
  • New ENTERPRISE: UPS redundancy and live migration (hosts and extra servers) can now be configured through the web interface too.
  • Changed: Monitoring integration (health endpoint, Prometheus, PRTG, SIEM event IDs) is now part of the Enterprise edition instead of Pro. Existing Pro licenses keep access permanently.
  • Fixed: several smaller issues found while building and reviewing the web interface, including a vertically misaligned language/theme switcher and a validation message that stayed German even in English mode.
  • New ENTERPRISE: The remote web interface's About page now shows whether a newer version is available (a "Check for updates" button, same source as the desktop auto-updater) — display only, no automatic download or install, since Server Core has no local session for a setup window to appear in. Shows the version, release notes, and links to the manual download and full changelog.
v1.8.1 September 1, 2026
  • New PRO: Topology tab — a graphical overview of every UPS, Hyper-V host, and extra server with protection status at a glance, including a PDF export as an emergency-plan attachment.
  • New PRO: Tamper Protection — the configuration file is digitally signed on every save; a change made outside the application is detected and logged the next time it starts.
  • New PRO: Previous-period comparison (trend arrows) and fleet overview in the Reports tab and in the PDF/e-mail report.
  • New: Host availability (SLA), battery health, and load trend are now also included in the PDF report and the email summary, not only in the GUI Reports tab.
  • Improved: Main menu restructured — Reports/Topology grouped under "Analysis", History/Log under "Logs", with a mouseover dropdown for quick access.
  • Fixed: several UI elements stayed permanently invisible due to a converter bug (Reports status line, battery events, sign-out button, History details).
v1.8.0 August 31, 2026
  • New PRO: Monitoring integration is now officially a Pro feature — with a native PRTG endpoint (/prtg) and a Prometheus endpoint (/metrics).
  • New PRO: SIEM integration via fixed event IDs in the Windows Event Log.
  • Improved: Live migration and VM suspend now detect a failure immediately instead of only after the full timeout.
  • Fixed: Several UPS-redundancy edge cases, including a global shutdown that ignored a host's opt-out.
  • New: Light color scheme (Dark / Light / System) under General Settings → Appearance.
  • New PRO: The health endpoint for monitoring integrations can now be fully configured from the GUI — including IP allowlist and a bearer token that can also be passed as a URL parameter.
  • New PRO: With multiple UPS units, the compact dashboard cards are now clickable; the runtime forecast now runs per UPS.
  • New PRO: UPS redundancy now supports an optional minimum-runtime safety margin — the covering UPS must itself have enough buffer left, otherwise the shutdown proceeds as planned.
  • Fixed: The auto-updater never displayed release notes.
v1.7.13 August 16, 2026
  • New PRO: UPS assignment for extra (non-Hyper-V) servers.
  • New PRO: Dedicated runtime threshold for the live-migration target.
v1.7.11 August 9, 2026
  • New PRO: Host SLA report — availability per Hyper-V host, correlated with the shutdown history.
  • New PRO: Expanded monitoring (health endpoint, host alerts).
v1.7.8 July 30, 2026
  • New: Custom OID profiles for exotic UPS models (SNMP).
  • New: Support for Socomec UPS units.
  • New: Hyper-V hosts and extra servers can now be duplicated.
  • New PRO: “Test Migration” button on the Hosts tab.
  • Fixed: Energy-consumption chart unreadable over long periods; live migration triggered too eagerly on brief voltage dips.
v1.7.7 July 28, 2026
  • New PRO: Live migration on power failure — VMs move to a healthy partner host instead of being shut down.
  • New: Extra (non-Hyper-V) servers are now part of the emergency shutdown.
v1.7.6 July 26, 2026
  • New: Input validation across all configuration dialogs.
  • New: Support-bundle export for faster diagnostics.
v1.7.4 July 21, 2026
  • Changed: Updates now run through the installer — more robust than the previous mechanism.
v1.7.3 July 9, 2026
  • New PRO: Dashboard status cards for multiple UPS units at once.
v1.7.0 June 22, 2026
  • New PRO: Support for multiple UPS devices at once.
v1.5.12 June 10, 2026
  • New: Electricity-cost calculation in reports.
  • New PRO: Monthly manager report as a PDF sent by email.
v1.5.5 June 9, 2026
  • New: VM suspend (Save-VM) as a gentler alternative to a full shutdown.