“Monitoring only” operating mode: watch UPS units without shutting anything down
UPSmonitor keeps polling the UPS, evaluates thresholds and sends alerts, but shuts nothing down. This page describes the operating mode in full: where it is set, what keeps running and what is dropped, what happens at the critical threshold, how the desktop app and the web interface present pure monitoring, and how the NOC display brings the state of all UPS units to a wall screen.
When the operating mode fits
UPS units at remote sites
Head office polls the branch office UPS units over VPN via SNMP or NUT. The software should not shut anything down there, but it should report power outages, the critical threshold and unreachability.
Plain UPS monitoring
Set globally, the interface hides Hyper-V hosts, VMs and additional servers. Hosts are then no longer checked for reachability either.
Decide per UPS
Individual UPS units are set to “Monitor only”, the others shut down their Hyper-V hosts in order as usual.
Status on the wall display
The NOC display shows all UPS units as large tiles, those needing attention first, and refreshes every 15 seconds without login.
Where to set the operating mode
The operating mode is part of the Enterprise edition. A UPS counts as “monitored only” if the global operating mode or its own option is set and an Enterprise license or the trial is active when the monitor starts.
| Where | Global (all UPS units) | Per UPS |
|---|---|---|
| Desktop app | “Service” tab, card “Operating mode (Enterprise)”: “Monitoring only (no shutdown)” | “UPS Settings” tab, card “UPS monitoring (Enterprise)”: “Monitor only (no shutdown)” |
| Web interface | “Service” page, section “Operating mode (Enterprise)” | “Edit UPS”, section “UPS monitoring (Enterprise)” |
| UPS importCSV or Excel | — | Column “Monitor only” (also “Monitoring only” or the German “Nur überwachen”), values yes/no, x, 1/0 |
config.json | "MonitoringOnlyMode": true | "MonitorOnly": true in the UPS entry under UpsDevices |
- Global takes precedence. If the global operating mode is active, the UPS form shows a note that “Monitoring only” already applies to all UPS units instead of the option. The value saved per UPS is kept.
- Without an Enterprise license the setting has no effect. In the desktop app the card is then locked. The web interface accepts the selection and states in red that “Monitoring only” is set but the service keeps shutting down automatically.
- Effective from the next start of the monitor. Switching during a power outage does not abort a shutdown that has already started.
What keeps running and what is dropped
Keeps running
- Polling of the UPS at the configured interval, over SNMP v1/v2c/v3 or NUT
- Alerts for power outage, mains return, “UPS unreachable”, bypass, UPS alarms and LOW BATTERY
- Warning thresholds for battery charge, load, battery temperature and input voltage, with alert and all-clear
- Measurements for trends, reports and the monthly report
- Health endpoint, Prometheus and PRTG, SNMP traps and Windows events
- The UPS self-test, manual or scheduled
Dropped
- Emergency shutdown of the assigned Hyper-V hosts and VMs
- Live migration of VMs to a partner host
- Early shutdown of additional servers based on remaining runtime
- Abort window and shutdown of the local machine
- Entry in the shutdown history, since nothing was shut down
Interaction with other UPS units
- Assigned hosts and servers stay up, even during a combined outage of several UPS units. A monitor-only UPS never counts toward the scope of a shutdown.
- Additional servers without a UPS assignment count as “belonging to every UPS”. If another UPS triggers a shutdown, they shut down with it. To prevent this, assign them explicitly to the monitor-only UPS.
- As a redundant second UPS or as the UPS of a migration target, it counts like any other: if it reports mains power, it holds back the shutdown of a host with two power supplies, and a migration target fed by it counts as powered.
- The configuration check warns when a Hyper-V host, a migration target or an additional server is assigned to a monitor-only UPS, because it will then not be shut down automatically during a power outage.
When the critical threshold is reached
The same thresholds as for a shutdown are evaluated: battery charge or remaining runtime on
battery at or below the configured value, LOW BATTERY, or a shutdown request from the UPS
(NUT FSD). A poll without a match resets the counter; a poll without a response
leaves it unchanged.
| What | Behaviour |
|---|---|
| Trigger | after the configured number of consecutive polls with a match (default 3) |
| Alertall configured channels | “🔴 UPS CRITICAL — threshold reached (monitoring only): UPS” with the reason and the note that no automatic shutdown takes place. Sent if the alert trigger “Emergency shutdown triggered” is enabled. |
| Windows event | Event ID 2003, warning, category Monitor |
| SNMP trapUPS-MIB format | upsTrapAlarmEntryAdded with upsAlarmLowBattery, on mains return upsTrapAlarmEntryRemoved |
| Log | “CRITICAL THRESHOLD REACHED — monitoring only, no shutdown” with the reason |
| Repetition | Once per outage. The next notification only follows after mains power has returned and failed again. |
| Mains return | The normal power-restored message; the monitor is armed again, Windows event 2002 |
If the UPS reports LOW BATTERY, the alert “UPS — BATTERY CRITICAL (Low Battery)” adds the note that this UPS is monitored only and that no automatic shutdown takes place.
License state, emergency shutdown, switching
The license state applies from the start of the monitor
If no Enterprise license is active at start, the software ignores the setting, keeps shutting down automatically and writes a warning to the log. If the license expires during operation or becomes valid during operation, the running monitor keeps its operating mode until it is restarted and reports the change once per run: in the log, as Windows event 1104 and through the alert channels.
- The manual emergency shutdown overrides the operating mode. The “EMERGENCY SHUTDOWN NOW” button on the desktop app dashboard also shuts down the hosts, servers and the local machine of monitor-only UPS units; the confirmation dialog says so. In global mode the button is hidden, so the exception concerns UPS units set to “Monitor only” individually. The web interface has no emergency shutdown.
- Switching aborts nothing. A shutdown that has already started runs to completion; the new operating mode applies from the next start of the monitor.
- No flag in the health endpoint.
/health,/metricsand PRTG rate a monitor-only UPS like any other: on battery is a warning, LOW BATTERY and unreachability are critical. “Shutdown In Progress” stays 0 because nothing is shut down.
What changes in global mode
Desktop app
- The “Hyper-V Hosts”, “Extra Servers” and “Virtual Machines” tabs are hidden
- The dashboard shows the banner “Monitoring only — no automatic shutdown”
- The host overview and the “EMERGENCY SHUTDOWN NOW” button are hidden
- Test mode, abort window, “Shut down local machine after Hyper-V hosts” and the migration thresholds are hidden; saved values are kept
Web interface
- The menu items “Hyper-V Hosts”, “Additional Servers” and “VMs” are missing
- The dashboard shows the banner and hides the host table
- On the service page, test mode, abort window and local machine are hidden
- Hosts and additional servers are no longer checked for reachability and do not count toward the overall status
If only some of the UPS units are set to “Monitor only”, the interface stays complete and hosts are still checked. Dashboard and table show no per-UPS flag; the NOC display marks such UPS units with “◉ Monitoring only”.
The dashboard in pure monitoring
The web interface dashboard is built for many UPS units. Above the table are the operating mode banner, the overall status with its reason and the counters; below them the table of all UPS units and the trend of battery charge and load.
| Element | Content |
|---|---|
| Banner | “◉ Monitoring only — no automatic shutdown. On power loss and at the critical threshold only warnings are sent.” |
| Overall status | OK, Warning, Critical or Unknown; except for OK with the reason in brackets, for example “1 UPS unreachable, 1 UPS on battery” |
| Counters | Total UPS units, on mains, on battery, unreachable, unknown, and on mains with bypass or alarm |
| Filters | “Show all” or “Needs attention only”; with sites, also one button per site that narrows table, counters and trend |
| Order | Low battery and unreachable first, then on battery, then unknown or on mains with bypass or alarm, finally on mains; alphabetical within the same level |
| Columns | Name, site, status with UPS alarm, battery, runtime, load, input voltage, battery health, last updated |
| Trend | Battery charge and load of a selectable UPS over 1 h, 6 h, 24 h or 7 days |
| Refresh | every 30 seconds; does not extend the login session |
Desktop app dashboard
- In global mode, the banner “Monitoring only — no automatic shutdown”, with the addition that only warnings are sent on power loss and at the critical threshold
- From two UPS units on, a summary — total UPS units, on mains, on battery, unreachable, unknown — and a choice between tiles and a compact table with one row per UPS
- A “Site” selector that limits tiles, table and summary to one site
- Trend of battery charge and load of the first UPS over 1 h, 6 h, 24 h or 7 days
- Refresh every 5, 15, 30 or 60 seconds, default 15, never faster than the poll interval of the UPS units
NOC display for the wall screen
The NOC display is a separate page of the web interface for a screen in the network operations centre or the server room. It shows each UPS as a large tile, orders them by severity and reloads every 15 seconds. A browser in full-screen or kiosk mode is enough; the page needs no JavaScript.
What the page shows
- Header with the counters critical, warning and OK, the number of unreachable hosts and the time of the snapshot
- One tile per UPS with status, battery, runtime, load and input voltage, below that active UPS alarms in plain text, bypass, “Replace battery”, a due battery replacement and “No current data since …”
- Badges for maintenance mode with end time, “◉ Monitoring only” for UPS units set that way individually, and the number of unacknowledged critical alarms
- “Hosts & servers” strip with the reachability of all Hyper-V hosts and additional servers, unreachable ones first; hidden in global “Monitoring only” mode
- Red banner while an emergency shutdown is running. Monitor-only UPS units do not trigger it.
For large fleets
- Attention first: critical, then warning, then OK; within the same level by status and name
- Grouped by site: one section per site with a coloured line, sites with problems first, UPS units without a site last
- Compact from 13 UPS units: UPS units that are OK only appear as name labels in a row, those needing attention remain large tiles
- Font size grows with screen width up to 4K; when opened via the NOC display link, the mouse pointer is hidden
- Narrow screens too: single column without horizontal scrolling
When a tile is red, yellow or green
| Level | Condition |
|---|---|
| Criticalred | LOW BATTERY, unreachable, shutdown in progress, no data yet, or last data older than 30 minutes |
| Warningyellow | On battery or status unknown, bypass, UPS alarm, “Replace battery”, data older than 10 minutes, or battery replacement overdue based on the installation date |
| OKgreen | All others; a maintenance window does not change the level, it only sets the badge |
Set up and secure
- Create the link: web interface, “Monitoring”, box “📺 NOC display”, “Create link”. Only administrators can do this, and the audit log records it.
- Set it as the start page on the display. The link is visible only right after it is created; only its SHA-256 hash is stored.
- Language: that of the administrator who creates the link. Append
?lang=enor?lang=deto the link to fix it. - Create new link invalidates the previous one immediately, Revoke link switches the display off. Invalid links return 404.
- Preview: signed-in users, including those with the “Read-only” role, open the page at
/noc.
No login, but read-only
Through the link the page is reachable without login and without session expiry, so a wall display is not signed out after the timeout. The link unlocks only this one page: no settings, no forms, links or scripts, GET only. The web interface's IP allowlist still applies; responses are not cached, pass on no referrer and are blocked for search engines. Anyone who knows the link can see the state of the UPS units, so it belongs on NOC display screens only.
In five steps
- Add UPS units. Individually or via UPS import from a CSV or Excel file, with site and the “Monitor only” column.
- Choose the operating mode. Globally on the “Service” tab or per UPS. In mixed operation, explicitly assign hosts and additional servers to their UPS.
- Check thresholds and alerts. Critical threshold and number of confirmations per UPS, warning thresholds as needed, and in the alert settings leave the trigger “Emergency shutdown triggered” enabled so that the critical threshold notification goes out.
- Save. The service reloads the configuration and restarts monitoring with the new operating mode — except during a power outage or a running shutdown. The log confirms for each UPS that it is monitored only.
- Set up the NOC display. Create the link and set it as the start page on the wall display; optionally connect the health endpoint to Prometheus, PRTG or Zabbix.
Frequently asked questions about “Monitoring only”
Which license do I need for “Monitoring only” and the NOC display?
The Enterprise license. The “Monitoring only” operating mode is part of the Enterprise edition, and the NOC display is part of the remote web interface, which also belongs to Enterprise. The 30-day trial unlocks all Enterprise features.
Can I only monitor some UPS units and keep automatic shutdown for others?
Yes. Each UPS has the option “Monitor only (no shutdown)”. UPS units without this option shut down their Hyper-V hosts and additional servers as usual. Hosts and servers should then be explicitly assigned to their UPS.
Are hosts on a monitor-only UPS shut down during a combined outage?
No. A monitor-only UPS never counts toward the scope of an automatic shutdown, not even when other UPS units fail at the same time. The exceptions are the manual emergency shutdown in the desktop app and additional servers without a UPS assignment, which count as “belonging to every UPS”.
How often does the software report the critical threshold?
Once per outage: as the alert “UPS CRITICAL — threshold reached (monitoring only)” through every configured channel if the alert trigger “Emergency shutdown triggered” is enabled, as Windows event 2003 and as an SNMP trap. After mains power returns, the monitor is armed again and reports the next outage.
What happens to the setting without an Enterprise license?
It is ignored: the software keeps shutting down automatically and writes a warning to the log at start-up. If the license expires during operation, the operating mode that applied at start stays in effect until the next start of the monitor, and the change is reported as Windows event 1104 and through the alert channels.
Does the wall display need to sign in to the web interface?
No. Under “Monitoring”, an administrator creates a NOC display link that opens only the NOC display page, without login and without session expiry. The link is visible only right after it is created, can be revoked or replaced by a new one at any time, and the web interface's IP allowlist still applies.
How many UPS units fit on one NOC display screen?
There is no fixed limit. From 13 UPS units on, the page shows UPS units that are OK only as name labels in a row, while those needing attention remain large tiles. In the example on this page, 36 UPS units at four sites fit on one 1920 × 1080 pixel screen this way.
Do Prometheus or PRTG recognise that a UPS is monitored only?
No. The health endpoint has no field for it and rates a monitor-only UPS like any other: on battery is a warning, LOW BATTERY and unreachability are critical. The metric for a shutdown in progress stays 0.
“Monitoring only” in the Enterprise edition
One-time license, 30-day free trial with all Enterprise features, including the web interface and the NOC display.