247-IT Guide
Eaton IPM alternative for Hyper-V
Eaton Intelligent Power Manager is a comprehensive data center tool. For pure Hyper-V environments the licensing model is what matters: every host counts as a node. A comparison of licensing, editions and Hyper-V integration.
Two Eaton products, two jobs
Buy an Eaton UPS and you will come across two programs. They do different jobs, and the choice between them decides effort and cost:
- Intelligent Power Protector (IPP) — a free agent installed on every computer you want to protect, which shuts down exactly that computer. For a single Hyper-V host on an Eaton UPS that is often enough. With several hosts it means one agent per host, one configuration per host and no shared order.
- Intelligent Power Manager (IPM) — central management with a web interface. IPM monitors UPS units, PDUs and other devices, controls hypervisors without an agent and runs as a Windows installation or a virtual appliance. Eaton sells IPM 2 in the Monitor, Manage and Optimize editions.
For several Hyper-V hosts with an ordered shutdown, IPM is the matching Eaton product. This comparison is about IPM.
What counts as a node in IPM
IPM 2 is licensed per node, either as a subscription or as a perpetual license with a limited update entitlement. According to Eaton's IPM 2 pricing overview, a node is a UPS or rack PDU, a hypervisor, a non-virtualized server or a storage system. Under IPM 1, only power devices counted.
| Environment | Nodes |
|---|---|
| 1 UPS, 3 Hyper-V hosts | 4 |
| 2 UPS units, 3 Hyper-V hosts, 1 physical file server | 6 |
| 2 UPS units, 6 Hyper-V hosts, 1 SAN | 9 |
The edition matters too. Host actions such as shutting down a hypervisor start with Manage. Actions on individual VMs, migration, load shedding and shutting down a cluster belong to Optimize. Every additional host therefore raises the license cost, and with a subscription it comes back every year.
Vendor information as of October 2026. Terms and editions may change; Eaton or your reseller can quote current prices.
Hyper-V integration in detail
According to its compatibility table, IPM 2 supports Hyper-V as a role and on Server Core, as well as System Center Virtual Machine Manager (SCVMM). Like the UPS Hyper-V Shutdown Monitor, it connects via WinRM without an agent on the hosts. Check two points from Eaton's documentation before you decide:
- WinRM authentication — the IPM 2.7 compatibility table lists WinRM with Basic authentication and unencrypted transport enabled for Hyper-V. That conflicts with common hardening guidelines. Ask Eaton what applies to your version. The UPS Hyper-V Shutdown Monitor uses Negotiate (Kerberos or NTLM, encrypted) by default and HTTPS on request.
- Cluster shutdown — the action that shuts down a cluster requires IPM to run outside the cluster. The same applies to any tool: whatever shuts down the cluster must not run on it. More in the guide Hyper-V failover cluster power outage.
Eaton IPM and UPS Hyper-V Shutdown Monitor compared
| Criterion | Eaton IPM 2 | UPS Hyper-V Shutdown Monitor |
|---|---|---|
| License | per node, subscription or perpetual with an update period | one-time license, €139 to €349 |
| More Hyper-V hosts | each host is another node | unlimited in every edition |
| Shutting down VMs | host actions from Manage, VM actions with Optimize | shut down or save per VM in every edition |
| Live migration instead of shutdown | migration with Optimize | from Pro |
| UPS units from other vendors | monitoring via RFC 1628 or NUT, shutdown based on them only with Optimize | APC, Eaton, Socomec, Vertiv, Huawei, CyberPower, RFC 1628 and NUT in every edition |
| Deployment | Windows or virtual appliance, web interface | Windows application and service, web interface in Enterprise |
| Other devices | PDUs, ATS, racks, storage systems, VMware | Hyper-V hosts and other Windows servers |
When Eaton IPM is the right choice
IPM plays to its strengths where there is more at stake than Hyper-V and a handful of UPS units:
- Large Eaton fleets — mass configuration of network cards and all device data in one interface.
- Data centers with PDUs and racks — power chains, rack views and environmental sensors are part of IPM.
- Mixed virtualization — when VMware vCenter or ESXi must be protected alongside Hyper-V.
- Existing Eaton framework agreement — when licenses and support already run through Eaton.
In a pure Hyper-V environment with a few UPS units, possibly from different vendors, IPM makes you pay for features you do not need, and extra for every host. The same reasoning for APC is in the guide PowerChute alternative for Hyper-V.
Decision checklist
- How many nodes add up? Count UPS units, hosts, physical servers and storage systems, for the next few years.
- Which edition do you need? If VMs should be shut down individually or migrated, it is Optimize.
- Are there UPS units from other vendors? Then check whether shutdown via RFC 1628 or NUT is included in your edition.
- Does the WinRM configuration meet your security policy? Basic authentication without encryption is not allowed in many environments.
- Do you need PDUs, racks or VMware? If yes, a lot speaks for IPM. If not, a specialized tool is enough.
Frequently asked questions
Is Eaton IPM free?
No. IPM 2 is licensed per node, as a subscription or as a perpetual license with a limited update entitlement. Eaton offers a trial of the Optimize edition. The free product is the Intelligent Power Protector (IPP) agent, which only shuts down the computer it is installed on.
What counts as a node in Eaton IPM?
According to Eaton's IPM 2 pricing overview, a UPS or rack PDU, a hypervisor, a non-virtualized server or a storage system. Three Hyper-V hosts on one UPS therefore make four nodes.
Can Eaton IPM trigger shutdowns from UPS units of other vendors?
IPM monitors other vendors' UPS units via RFC 1628 (SNMP) or NUT. According to Eaton's compatibility list, shutdown based on them requires the Optimize license.
Can I run Eaton IPM and the UPS Hyper-V Shutdown Monitor side by side?
Yes, both read the UPS via SNMP. Only one tool should shut down the same hosts, though. Add no hosts to the other one or use it for monitoring only, for example with the Enterprise edition's monitoring-only mode.
More guides
Replacing UPS batteries
Ageing, warning signs and swapping without a protection gap.
Restarting after a power outage
Starting servers, storage and VMs automatically when power returns.
Hyper-V on Server Core
Protecting hosts without a desktop via WinRM or a web interface.
Shutting down Hyper-V VMs in a power outage
Stop action, shutdown order and time budget for an orderly shutdown.
SNMPv3 on a UPS network card
authPriv with SHA and AES instead of a plain-text community.
NUT on Windows
Query a UPS via Network UPS Tools from a NAS or Linux server.
Hyper-V failover cluster power outage
Coordinating quorum, CSV and live migration.
Active Directory & power outages
The USN rollback myth and the real risks for domain controllers.
SQL Server & Exchange on Hyper-V
Protecting databases during a power outage.
Calculating UPS runtime
Why the datasheet runtime rarely holds.
PowerChute alternative for Hyper-V
UPS shutdown without vendor lock-in.
Monitoring UPS units from multiple vendors
One tool instead of several silos.
Protect Hyper-V hosts without node licensing
30 days free, every feature included. One one-time license for unlimited Hyper-V hosts, with Eaton UPS units and any other SNMP- or NUT-capable UPS.