Monitoring a three-phase UPS: reading phase values L1 to L3
A three-phase UPS reports voltage, current, power and load per phase. If you poll a single value, a phase failure on L2 or L3 goes unnoticed. How the MIBs of RFC 1628, Eaton, Socomec and Huawei and NUT expose the phases, where 230 and 400 V get mixed up, and how the UPS Hyper-V Shutdown Monitor derives load, power and warning thresholds from them.
Why one reading is not enough on three-phase power
Most UPS tools poll exactly one SNMP value for input voltage and one for load. For a single-phase rack UPS that is correct. For a three-phase UPS such as a Socomec Masterys, an Eaton 93PM or a Huawei UPS5000, however, that value is only row 1 of the input table, that is phase L1. Whatever happens on L2 and L3 stays invisible. Three cases that slip through:
- Phase failure on L2 or L3 — a breaker trips or one line drops out in the sub-distribution. L1 still shows 230 V, the UPS runs partly on battery depending on the model or just raises an alarm. The monitoring sees a healthy UPS.
- Unbalanced load — the power supplies in the rack were not spread evenly across the phases. The UPS sits at 40% total load, but L3 carries 85%. At the next rebuild exactly that phase tips into overload and the UPS goes to bypass.
- 3:1 units — three-phase input, single-phase output, typical for 10 to 20 kVA in a small data centre. There are three input voltages but only one output row. A tool that reads input and output with the same phase count shows nonsense or nothing for the output.
For the shutdown decision during a power outage, the battery status is sufficient even on three-phase units: if the input fails, the UPS reports battery operation and the hosts shut down as planned. The phase values show whether the installation is healthy before that. The basics are in the guide UPS monitoring without shutdown.
Phase-to-neutral, line-to-line and decivolts
A 400 V three-phase grid has two voltages: between one phase and neutral there are about
230 V (phase-to-neutral, L1–N), between two phases about 400 V
(line-to-line, L1–L2). The factor between them is √3. The UPS-MIB of RFC 1628 defines
upsInputVoltage as the RMS value per input line, but does not state whether the vendor
reports phase-to-neutral or line-to-line. Most cards deliver phase-to-neutral, some firmwares the
line-to-line voltage. NUT keeps them apart: input.L1-N.voltage versus
input.L1-L2.voltage.
Then there is the unit. RFC 1628 and Eaton report whole volts, Socomec NetVision and Huawei decivolts, that is 2300 for 230.0 V. Some RFC 1628 agents do the same, contrary to the MIB. UPSmonitor therefore applies the same heuristic to every voltage: a value above 600 is divided by 10. 2300 becomes 230 V, 4000 becomes 400 V, and a genuine line-to-line voltage of 400 stays 400 because it is below the limit. The limit sits deliberately above any low-voltage grid and below any plausible decivolt value of a grid.
How the MIBs model the phases
All supported MIBs follow the same pattern: a count object for the number of phases and a table whose rows are the phases. The differences lie in the units and in which columns are missing.
| Source | Phase count | Tables and units | What is missing |
|---|---|---|---|
| RFC 1628 (UPS-MIB) Vertiv, Riello, generic cards | upsInputNumLines, upsOutputNumLines | upsInputTable voltage in V; upsOutputTable voltage V, current 0.1 A, power W, load %. Row n = phase n. | Nothing in the standard; some agents fill only row 1 or report decivolts. |
| Eaton XUPS-MIB 93PM, 9PX, 9SX with Network-M2/-MS | xupsInputNumPhases, xupsOutputNumPhases | xupsInputTable voltage V; xupsOutputTable voltage V, current A, real power W, all in whole units. | No load per phase — xupsOutputLoad is the total only. |
| Socomec NetVision 5 and 7 Masterys, Modulys, Netys | upsInputNumLines, upsOutputNumLines in its own tree under 4555 | Layout like RFC 1628, but voltage in decivolts and current in 0.1 A; load in %. Two tree generations (.1.1.1.1 and .1.1.7.1). | No real power per phase. |
| Huawei HUAWEI-UPS-MIB UPS2000, UPS5000 | hwUpsCtrlInputStandard (1 = single-phase, 2 = three-phase), marked obsolete in the MIB | No rows but fixed columns A/B/C in hwUpsInputTable and hwUpsOutputTable: voltage 0.1 V, current 0.1 A, load 0.1%, real power 0.1 kW. | Not all cards deliver the phase count; then all three columns have to be read and the populated ones counted. |
| NUT over 100 vendors per the compatibility list | input.phases, output.phases | input.Ln-N.voltage, output.Ln-N.voltage, output.Ln.current, output.Ln.realpower, output.Ln.power.percent, in V, A, W and %. | Depends on the driver; many drivers set the variables only when the UPS delivers them. |
A 3:1 unit reports 3 for the input and 1 for the output. Rows 2 and 3 of the output
table then do not exist or answer with noSuchInstance. A clean reader polls both count
objects and leaves the missing output columns empty instead of filling them with zeros. How to
secure the card with SNMPv3 for this is in the guide
SNMPv3 on a UPS network card.
How UPSmonitor reads and summarises the phase values
The UPS Hyper-V Shutdown Monitor reads the phase count first on every
poll. If the UPS reports more than one phase, it fetches rows 1 to 3 of the input and output tables
in an additional SNMP batch, row 1 included again so that all phases come from the same poll.
Single-phase units cost no additional round trip. Huawei cards without
hwUpsCtrlInputStandard are read across all three columns, and the populated ones are
counted.
The phase values produce the summary values that appear everywhere else in the software:
- Load — the highest phase load, not the average. A UPS at 25, 30 and 85% shows 85%, because that phase limits the unit. If the MIB has no load per phase (Eaton XUPS), the unit's total value remains.
- Output power — the sum of the phases as soon as at least two phases report real power. Otherwise the single value from the MIB.
- Input voltage and output current — as single values they stay phase L1, just as the front panel of many units does. The three individual values are in the phase display.
- Voltages — every phase voltage passes through the decivolt detection from section 02.
The per-phase values appear in four places:
- Desktop dashboard — below the additional measurements, one row per phase with input voltage, load and power, as far as the unit delivers them.
- Web interface — a “Phases” table with one row per UPS and phase: input voltage, output voltage, current, power, load. Columns without values are omitted.
/health— the JSON carriesphases,inputPhaseCountandoutputPhaseCountper UPS.- Prometheus and PRTG —
/metricsprovides the familiesupshypervshutdown_ups_phase_input_voltage_volts,_output_voltage_volts,_output_current_amperes,_output_power_wattsand_load_percentwith the labelphase="L1"to"L3", plus_input_phasesand_output_phases./prtgappends channels such as “UPS — L1 Input Voltage” to the end of the channel list; because of the PRTG limit of 50 channels they are the first to be cut off with many UPS units.
The phase values are part of the additional measurements (Pro). Web interface, health endpoint, Prometheus metrics and PRTG format belong to the Enterprise edition. Only what the UPS actually reports is shown.
Warning thresholds on the worst phase
A warning threshold that checks only L1 misses exactly the cases from section 01. On three-phase units the warning thresholds (Enterprise) therefore always evaluate the phase most likely to breach the threshold:
- Undervoltage — the lowest input voltage of all phases. If L2 drops to 0 V, the threshold fires even though L1 sits at 230 V. Checked on mains only; on battery the input voltage is gone by nature, and the power outage alert already reports that.
- Overvoltage — the highest input voltage of all phases.
- Load — the highest phase load, the same value the dashboard shows as load.
As with all warning thresholds: triggered only after two consecutive polls, cleared with hysteresis, reported over the configured alert channels, Windows event 2004 and SNMP trap. Set the load threshold so that a single overloaded phase stands out, say 80%, not only the total value, which is much lower with an unbalanced distribution.
What you have to check on your own unit
- Line-to-line or phase-to-neutral — whether your card reports 230 or 400 V per phase is decided by the firmware, not the MIB. Compare the first value on the dashboard with the display on the unit and set the voltage warning thresholds accordingly. The shutdown is not affected; it depends on the battery status.
- Implemented without a test unit — columns and units come from the public MIB files (UPS-MIB, XUPS-MIB, SOCOMECUPS-MIB, HUAWEI-UPS-MIB) and the matching NUT drivers, replayed through a fake SNMP agent in 34 test cases. No real Masterys or UPS5000 was on the bench. If your unit deviates, an SNMP walk of the tables will tell.
- Huawei real power per phase — the MIB names kW as the unit with a range of ±12000. 0.1 kW is assumed, as for all other Huawei values. If your unit shows ten times or a tenth of the power, that is why.
- Phase count not reported — without a count object the software reads only row 1, except for Huawei. An RFC 1628 agent that does not answer
upsInputNumLinesstays single-phase even if rows 2 and 3 exist.
Which vendors the software knows natively beyond that, and where RFC 1628 serves as the fallback, is in the guide Monitoring UPS units from multiple vendors.
Three-phase UPS checklist
- Phase count visible — the dashboard shows three rows L1 to L3, with empty output columns for L2 and L3 on 3:1 units.
- Voltage reference clarified — the displayed value matches the unit's display (about 230 or 400 V), and the voltage warning thresholds are set accordingly.
- Load plausible — the displayed load matches the highest phase on the unit; the load distribution in the rack is known.
- Load threshold set — so that a single phase stands out before it forces the UPS into bypass.
- Phase failure tested — in a maintenance window, disconnect one input phase and check that the undervoltage warning and the unit's alarm arrive.
- Runtime under real load — the runtime of a three-phase UPS depends on the total load, not on one phase. See Calculating UPS runtime.
Frequently asked questions
Why does the dashboard show only one input voltage for my three-phase UPS?
On a three-phase UPS the single “input voltage” value is always phase L1, just as the front panel of many units reports it. The values of all three phases are in the phase display below it (Pro). If that is missing, the UPS does not report its phase count or returns no values for L2 and L3.
What does the load percentage mean on a three-phase UPS?
UPSmonitor shows the highest phase load as the load, not the average. A UPS at 25, 30 and 85% on its three phases shows 85%, because that phase limits the unit. The per-phase values are shown next to it.
My UPS reports 400 V instead of 230 V. Is that a bug?
Not necessarily. Some firmwares report the line-to-line voltage between two phases (about 400 V) instead of the phase-to-neutral voltage (about 230 V). Which one your card delivers can only be checked at the unit. It does not affect the shutdown, but it does affect voltage warning thresholds.
Does the phase display work with a 3:1 UPS?
Yes. With a three-phase input and a single-phase output, rows L2 and L3 carry input values only and the output columns stay empty. The software reads the phase count separately for input and output.
More guides
Sizing a UPS for Hyper-V
Calculating VA, runtime and the shutdown time budget.
Socomec, Vertiv and Huawei via SNMP
Prepare the card, understand the MIB trees, check the values.
Monitoring UPS units from multiple vendors
One tool instead of several silos.
SNMPv3 on a UPS network card
authPriv with SHA and AES instead of a plain-text community.
UPS monitoring without shutdown
Monitor and alert without shutting anything down.
Calculating UPS runtime
Why the datasheet runtime rarely holds.
Replacing UPS batteries
Warning signs, self-test and planning without a protection gap.
NUT on Windows
Query a UPS via Network UPS Tools from a NAS or Linux server.
Eaton IPM alternative for Hyper-V
Node licensing, editions and Hyper-V integration compared.
Hyper-V failover cluster power outage
Coordinating quorum, CSV and live migration.
UPS alerts via Microsoft 365 and Teams
Graph instead of SMTP AUTH, Workflows instead of connectors.
Shutting down Hyper-V VMs in a power outage
Stop action, shutdown order and time budget for an orderly shutdown.
Restarting after a power outage
Starting servers, storage and VMs automatically when power returns.
PowerChute alternative for Hyper-V
UPS shutdown without vendor lock-in.
Keep all three phases in view
30 days free, every feature included. With phase values L1 to L3 via SNMP and NUT, warning thresholds on the worst phase, and Prometheus and PRTG integration.